DocumentCode :
1585202
Title :
Impulse breakdown performance of the ice surface
Author :
Farzaneh, M. ; Brettschneider, S. ; Srivastava, K.D. ; Li, S.Y.
Author_Institution :
Atmos. Icing of Power Network Equip., Quebec Univ., Chicoutimi, Que., Canada
Volume :
4
fYear :
1999
fDate :
6/21/1905 12:00:00 AM
Firstpage :
341
Abstract :
The main purpose of the present study is to further understanding of ice surface breakdown. The effects of several parameters such as air temperature, freezing water conductivity and voltage polarity on the 50% lightning impulse breakdown voltage were investigated. An electrode configuration of two metallic hemispherical capped rods of 12 mm in diameter half submerged in ice was used for all experiments. The results showed that an increase in air temperature or freezing water conductivity led to a decrease in the breakdown voltage of the ice surface. The influence of voltage polarity on the breakdown voltage depended on ambient air temperature and freezing water conductivity
Keywords :
ice; 12 mm; air temperature; ambient air temperature; electrode configuration; freezing water conductivity; ice surface breakdown; impulse breakdown performance; lightning impulse; metallic hemispherical capped rods; voltage polarity;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990862
Filename :
821290
Link To Document :
بازگشت