• DocumentCode
    1585581
  • Title

    Investigation on the phase selection criterion based on improved modular fault component

  • Author

    Lin, Xiangning ; Zhao, Zhimin ; Bo, Zhiqian

  • Author_Institution
    Coll. of Electr. Eng. & Inf. Technol., Three Gorges Univ., Yichang, China
  • fYear
    2009
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Under the conditions of the various system parameters and fault types, the performance of the phase selector based on modular fault component are analyzed. Compared with the phase selector based on difference of two phase currents, this phase selector is better in terms of overall performance. However, this phase selector cannot achieve theoretical selectivity for a real fault. Furthermore, this phase selector may lack of sensitivity where the relay is equipped on the side of weak source. So an improved scheme is presented to make up for above shortcomings, and the EMTP simulation has shown that the improved scheme is effective.
  • Keywords
    power system faults; power system protection; EMTP simulation; improved modular fault component; phase currents; phase selection criterion; phase selector; system parameters; Circuit faults; EMTP; Educational institutions; Impedance; Linear circuits; Performance analysis; Relays; Switches; Tellurium; Voltage; difference of phase currents; modular fault component; phase-selector; phase-selector based voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275596
  • Filename