• DocumentCode
    1585754
  • Title

    Research on the recovery fresh air heat pump units applications in the cold and serious cold regions

  • Author

    Chen Aoxue ; Ran Chunyu ; Liu Hailong

  • Author_Institution
    School of Municipal & Environmental Engineering, Jilin Institute of Architectural and Civil Engineer, Changchun, China
  • fYear
    2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    In order to solve the air-source heat pump can not work well in the cold and serious cold regions. This article carries on the theory and experimental study to the recovery fresh air heat pump units, with the recycled exhaust heat to heat fresh air, has mastered the system operation characteristics and the actual operating results. The experimental results show that the indexes meet the needs of load for heating in winter. The coefficient of performance (COP) is in the value of more than 3.80, and the heat recovery efficiency is up to 82%, which is prolonging the heat pump units and the fresh air units running in the period of heating, maintaining well Indoor Air Quality(IAQ) for a long time.
  • Keywords
    heat recovery efficiency; the coefficient of performance(COP); the cold and severe cold regions; the recovery fresh air heat pump units;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    World Automation Congress (WAC), 2012
  • Conference_Location
    Puerto Vallarta, Mexico
  • ISSN
    2154-4824
  • Print_ISBN
    978-1-4673-4497-5
  • Type

    conf

  • Filename
    6321500