DocumentCode :
1590042
Title :
High-frequency oscillations in a power transformer
Author :
Dernetriades, G.D. ; Manias, S.N. ; Ranstad, P.
Author_Institution :
Power Eng. Dept., ABB Corp. Res., Vasteras, Sweden
Volume :
2
fYear :
2001
fDate :
6/23/1905 12:00:00 AM
Firstpage :
612
Abstract :
Power transformers are widely used as step-up or step-down devices and they can offer galvanic isolation between the input of the power supply and the output. When the operating frequency is considerably high, transformer parasitics are of importance. Interleaving of the transformer windings causes a reduction of the leakage inductance. However, the winding capacitance and the stray capacitance increases due to the good proximity of the windings achieved by interleaving
Keywords :
capacitance; circuit oscillations; inductance; power supplies to apparatus; power transformers; transformer windings; high-frequency oscillations; leakage inductance; operating frequency; power transformers; step-down devices; step-up devices; stray capacitance; transformer parasitics; transformer windings interleaving; winding capacitance; Conducting materials; Dielectrics and electrical insulation; Frequency; Galvanizing; Inductance; Interleaved codes; Parasitic capacitance; Permittivity; Power supplies; Power transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2001. PESC. 2001 IEEE 32nd Annual
Conference_Location :
Vancouver, BC
ISSN :
0275-9306
Print_ISBN :
0-7803-7067-8
Type :
conf
DOI :
10.1109/PESC.2001.954183
Filename :
954183
Link To Document :
بازگشت