• DocumentCode
    1591674
  • Title

    Parallel control of the UPS inverters with frequency-dependent droop scheme

  • Author

    Chiang, S.J. ; Chang, J.M.

  • Author_Institution
    Dept. of Electr. Eng., Nat. Lien-Ho Inst. of Technol., Miao-Li, Taiwan
  • Volume
    2
  • fYear
    2001
  • fDate
    6/23/1905 12:00:00 AM
  • Firstpage
    957
  • Abstract
    This paper presents a control approach for paralleling the UPS inverters with no control interconnection. The reference voltage of the inverter is generated to simulate a reactor connected between the inverter and the load at the fundamental frequency. The intention is to control the real and reactive power sharing of the inverters with the Q-V and P-ω droop scheme without connection of a true transfer reactor. At the harmonic frequency the reference voltage turns to simulate a resistor, aiming that the load harmonic current can be shared equally and the voltage distortion is low. Two 1 kVA inverters are setup for demonstrating the effectiveness of the proposed approach
  • Keywords
    electric current control; invertors; power conversion harmonics; reactive power control; uninterruptible power supplies; 1 kVA; UPS inverters paralleling; current sharing control; frequency-dependent droop scheme; harmonic frequency; load harmonic current sharing; parallel control; reactive power sharing control; reactor simulation; real power sharing control; reference voltage generation; resistor simulation; voltage distortion; Automatic control; Circuit simulation; Frequency; Impedance; Inductors; Inverters; Power system harmonics; Power system interconnection; Uninterruptible power systems; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Specialists Conference, 2001. PESC. 2001 IEEE 32nd Annual
  • Conference_Location
    Vancouver, BC
  • ISSN
    0275-9306
  • Print_ISBN
    0-7803-7067-8
  • Type

    conf

  • DOI
    10.1109/PESC.2001.954243
  • Filename