Arc flash considering generator decrement curves
Author :
Grainger, Lance ; Leschert, Duane ; Bennett, Andrew ; Zehr, Kent
Author_Institution :
Grainger Electr. Res., Edmonton, AB, Canada
fYear :
2014
fDate :
8-10 Sept. 2014
Firstpage :
279
Lastpage :
288
Abstract :
The purpose of this paper is to outline a method for calculating IEEE Std. 1584-2002 arc flash incident energy, taking into account the decrement in generator supplied fault current. The magnitude of fault current, for faults located close to generators, decrement rapidly. Arc flash exposure energy is calculated on a cycle by cycle basis for the duration of the fault. The energy during each cycle is then summed. Decremented fault results are compared to results from ANSI fault methods.
Keywords :
arcs (electric); electric generators; flashover; ANSI fault methods; IEEE Std. 1584-2002 arc flash incident energy; arc flash; arc flash exposure energy; generator decrement curves; generator supplied fault current; Arc discharges; Fault currents; Generators; Impedance; Induction motors; Resistance; Standards; Arc Flash; Dynamic Fault Modeling; Fault Current; Generator Decrement;