• DocumentCode
    1593034
  • Title

    Fault location for double-circuit lines utilizing sparse voltage measurements

  • Author

    Kang, Ning ; Liao, Yuan

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Kentucky, Lexington, KY, USA
  • fYear
    2009
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    This paper presents a general method for pinpointing location of faults on a double-circuit transmission line by employing only voltage measurements at one or two buses based on the bus impedance matrix technique. The bus impedance matrix of the network with the addition of a fictitious bus at the fault point for each sequence network is constructed as a function of fault location. Fault location can then be derived from fault analysis utilizing the expanded bus impedance matrices. The distinctive feature of this method is that measurements can be from buses other than those of the faulted line. The proposed approach assumes that the network data is available. Quite accurate results have been obtained based on simulation studies.
  • Keywords
    fault location; impedance matrix; power transmission lines; power transmission protection; voltage measurement; bus impedance matrix technique; double-circuit transmission line; fault analysis; fault location; network data; sequence network; simulation; sparse voltage measurement; Circuit faults; Fault location; Impedance; Power system faults; Power system reliability; Power system simulation; Power transmission lines; Transmission line matrix methods; Transmission line measurements; Voltage measurement; Fault location; bus impedance matrix; double-circuit transmission line; voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275846
  • Filename
    5275846