  • Abstract
    Preventive diagnosis and maintenance of transformers has become more and more useful in recent times in order to improve the reliability of electric power systems. Time domain dielectric testing techniques such as return voltage (RV) measurement and polarisation-depolarisation current (PDC) measurement have recently been widely used as potential tools for condition assessment of transformer insulation. In the frequency domain, measurement of the dissipation factor (tandelta) over a frequency range of 0.1 mHz to 1 kHz has been commonly used to assess the condition of transformer insulation. A number of transformers have been tested with these diagnostic techniques. A better understanding and analysis of the dielectric test results is only possible with a clear understanding of the physical behaviour of the insulation system in response to moisture and ageing. A circuit model, which describes the dielectric behaviour of the transformer´s main insulation system, has been modelled in this paper from the frequency domain measurement data and then RV and PDC data have been simulated from the circuit model. This paper then presents discussions of frequency and time domain techniques to find the condition of transformer insulation in terms of moisture and ageing estimation.
  • Keywords
    dielectric polarisation; electric current measurement; power system reliability; power transformer insulation; power transformer testing; time-frequency analysis; voltage measurement; PDC data; RV; ageing estimation; condition assessment; dielectric testing technique; dissipation factor measurement; electric power system reliability; frequency-time domain analysis; moisture estimation; polarisation-depolarisation current measurement; power transformer; return voltage measurement; Current measurement; Dielectric measurements; Dielectrics and electrical insulation; Frequency domain analysis; Insulation testing; Polarization; Power system reliability; Power transformer insulation; Power transformers; Time measurement; Ageing and Moisture Analysis; Dielectric Response; Dissipation Factor; Insulation Model Nomenclature; Oil/paper Insulation; Polarisation Depolarisation Current; Return Voltage; Transformer Condition Monitoring;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275851
  • Filename
    5275851