• DocumentCode
    1594231
  • Title

    Analysis of partial discharge phenomena in paper-oil insulation systems as a basis for risk assessment evaluation

  • Author

    Cavallini, A. ; Montanari, G.C. ; Ciani, F.

  • Author_Institution
    Dip. Ingegneria Elettrica, Viale Risorgimento, Bologna, Italy
  • fYear
    2005
  • Firstpage
    241
  • Lastpage
    244
  • Abstract
    Partial discharge (pd)-based risk assessment in electrical insulation systems becomes effective only if the nature of the defect generating pd can be ascertained. In oil/paper insulation systems this is a fundamental item since e.g. harmfulness of pd generated by gas bubbles is much smaller than that of pd occurring between paper layers. For such reasons, partial discharge analysis of oil/paper insulated systems often lacks a clear correlation between cause (i.e., defect type) and effect (partial discharge recording). Results relevant to partial discharge measurements performed on lab-scale objects having different electrode configuration are presented in the paper with the purpose to spotlight characteristic features aimed at identifying the basic nature of partial discharge-generating defects in oil/paper insulated systems.
  • Keywords
    electrodes; paper; partial discharge measurement; risk management; transformer oil; electrical insulation systems; electrode configuration; paper-oil insulation systems; partial discharge measurements; partial discharge recording; partial discharge-generating defects; risk assessment evaluation; Cause effect analysis; Dielectrics and electrical insulation; Disk recording; Gas insulation; Oil insulation; Partial discharge measurement; Partial discharges; Petroleum; Risk analysis; Risk management;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Dielectric Liquids, 2005. ICDL 2005. 2005 IEEE International Conference on
  • Print_ISBN
    0-7803-8954-9
  • Type

    conf

  • DOI
    10.1109/ICDL.2005.1490071
  • Filename
    1490071