• DocumentCode
    1597232
  • Title

    Non-linear load modeling — Requirements and preparation for measurement

  • Author

    Rudion, K. ; Guo, H. ; Abildgaard, H. ; Styczynski, Z.A.

  • Author_Institution
    Otto-von-Guericke-Univ. Magdeburg, Magdeburg, Germany
  • fYear
    2009
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    The existing software for the simulation of power system operation uses mostly simple load models such as the constant power load model, the constant impedance load model or the static polynomial load model to represent the real system load characteristic. In some cases using such load models in power system dynamic simulation may produce inaccurate results and lead to inappropriate system operation. In this paper load modeling using field measurement data from a load bus in the power grid to improve the simulation accuracy in the study of power system stability is discussed. The goal is to investigate the influence of different perturbations in the power grid on load behaviors as preparation for field measurement. Furthermore, there is a focus on the definition of measurement requirements. In addition, the nonlinear least-squares algorithm used to identify load model is discussed. As preparation, a complex nonlinear load model with predetermined parameters will be simulated in some defined scenarios, the simulation results are compared with a constant power load model. By using the transformer tap changer to make perturbations in the power system, the load dynamic characteristics could be gathered, and the perturbations data could be used to identify the parameters of the non-linear load model.
  • Keywords
    least squares approximations; power grids; power system simulation; power system stability; constant impedance load model; constant power load model; field measurement data; load dynamic characteristics; nonlinear least-squares algorithm; nonlinear load modeling; power grid; power system dynamic simulation; power system operation simulation; power system stability; real system load characteristic; static polynomial load model; transformer tap changer; Impedance; Load modeling; Polynomials; Power grids; Power measurement; Power system dynamics; Power system measurements; Power system modeling; Power system simulation; Power system stability; Nonlinear Least-Squares algorithm; Power system simulation; Transformer Tap changing; non-linear load model;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275994
  • Filename
    5275994