DocumentCode
1601448
Title
Quenching of Partial Discharges in medium voltage networks by traditional arc suppression coil
Author
Rozenkrons, J. ; Sults, V. ; Priedite, I.
Author_Institution
Riga Tech. Univ., Riga, Latvia
fYear
2010
Firstpage
203
Lastpage
206
Abstract
In this article, we describe a possibility to quench Partial Discharges (PD) in medium voltage networks by using Residual Current Compensation (RCC) device (Swedish Neutral), proposed by K. Winter. If voltage network phase PD activity increases in one of medium, the RCC device shifts network neutral potential in such a way, that voltage of spoiled phase to earth decreases below PD extinction level. The expensive RCC device is necessary. There is a cheaper way for this purpose to use traditional arc suppression coil with auxiliary power winding. In case of increasing PD activity it is possible to inject in coil auxiliary winding a proper voltage, which diminishes the network spoiled phase voltage and decreases PD activity. The main aim of this article is to show the possibility to use arc suppression coils auxiliary power winding for quench of PD in medium voltage networks and to substitute a more expensive RCC device.
Keywords
coils; partial discharges; power apparatus; windings; arc suppression coil; auxiliary power winding; medium voltage equipment; medium voltage networks; partial discharges; quenching; residual current compensation; Analytical models; Coils; Fault tolerance; Hardware design languages; Information analysis; Medium voltage; Microcontrollers; Microprocessors; Partial discharges; Transient analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Quality and Supply Reliability Conference (PQ), 2010
Conference_Location
Kuressaare
Print_ISBN
978-1-4244-6978-9
Type
conf
DOI
10.1109/PQ.2010.5549995