DocumentCode :
1602345
Title :
Using a cascaded H-bridge STATCOM for rebalancing unbalanced voltages
Author :
Betz, R.E. ; Summers, T.J.
Author_Institution :
Sch. of Electr. Eng. & Comput. Sci., Univ. of Newcastle, Newcastle, NSW
fYear :
2007
Firstpage :
1219
Lastpage :
1224
Abstract :
This paper considers specific issues related to using the cascade (also known as the H-bridge) multilevel STATCOM with unbalanced voltages and currents at the STATCOM-AC line connection terminals. Under this condition the average power into the individual phase legs of the converter, in general, is not zero, although the total three phase power is zero. The resultant phase cluster power unbalance can result in increasing or decreasing capacitor voltages within a phase leg. This paper will present a technique for zeroing the phase cluster average power under unbalanced line conditions when the control strategy is to rebalance unbalanced voltages.
Keywords :
bridge circuits; power convertors; static VAr compensators; voltage control; STATCOM-AC line connection terminals; cascaded H-bridge STATCOM; multilevel STATCOM; phase cluster power unbalance; rebalancing unbalanced voltages; Adders; Automatic voltage control; Capacitors; Computer science; Energy storage; Leg; Power electronics; Reactive power; Topology; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics, 2007. ICPE '07. 7th Internatonal Conference on
Conference_Location :
Daegu
Print_ISBN :
978-1-4244-1871-8
Electronic_ISBN :
978-1-4244-1872-5
Type :
conf
DOI :
10.1109/ICPE.2007.4692571
Filename :
4692571
Link To Document :