DocumentCode
1605373
Title
A novel algorithm of wide area backup protection based on fault component comparison
Author
He, Zhiqin ; Zhang, Zhe ; Yin, Xianggen ; Wang, Hua
Author_Institution
Electr. Power Security & High Efficiency Lab., Huazhong Univ. of Sci. & Technol., Wuhan, China
fYear
2010
Firstpage
1
Lastpage
7
Abstract
This paper proposes a novel wide area back-up protection algorithm that measures synchronized information from different buses in region. The amplitude of voltage fault component from different buses is compared, and the bus with maximum magnitude will be selected. Hence, suspected fault line set could be established according to the sub-graph and complete incidence matrix of selected buses. Then, voltage fault component amplitude at two sides of each suspected line could be calculated from another side, and the amplitude comparison between computed and measured value could be implemented. The ratio would be 1 when external fault occurs, and it would be greater than 1 when internal fault occurs. Thus, the fault line could be identified finally. The technique doesn´t need high precision synchronization of wide area information, and could response to different faults. The simulation of 10-unit and 39-bus New England system using PSCAD/EMTDC illustrates the effectiveness of this method.
Keywords
fault diagnosis; graph theory; power system protection; synchronisation; EMTDC; PSCAD; complete incidence matrix; fault component; fault line; sub-graph; synchronization; wide area backup protection; Bismuth; Synchronization; 10-unit and 39-bus New England system; PSCAD/EMTDC; Wide area protection; fault component comparison; phasor measurement unit(PMU);
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2010 International Conference on
Conference_Location
Hangzhou
Print_ISBN
978-1-4244-5938-4
Type
conf
DOI
10.1109/POWERCON.2010.5666146
Filename
5666146