• DocumentCode
    1605812
  • Title

    Applying capacitors to maximize benefits of conservation voltage reduction

  • Author

    McCarthy, C.A. ; Josken, J.

  • Author_Institution
    Syst. Eng. Group, Cooper Power Syst., Franksville, WI, USA
  • fYear
    2003
  • Abstract
    There are economic and reliability benefits for reducing peak loading of distribution feeders. Many cooperative and municipal utilities pay a demand charge based on peak usage, so there can also be an economic incentive to reduce peak demand. As experienced in some areas of the country, it is possible for the load to approach or exceed the total available generation. This leads to high prices on the electric power spot market, and it may lead to some customers experiencing outages due to a lack of generation. In some situations, conservation voltage reduction can be implemented to temporarily reduce the load demand on individual feeders. Lowering substation voltage for peak shaving can be done without compromising power quality if distribution lines are properly compensated with power factor correction and/or voltage regulation devices. This paper describes a methodology of using multiple distributed capacitor banks on feeders to achieve the flat voltage profile required for successful implementation of conservation voltage reduction.
  • Keywords
    capacitor storage; load (electric); power control; power distribution economics; power distribution reliability; power factor correction; substations; voltage control; capacitors; conservation voltage reduction; cooperative utilities; demand charge; distribution lines compensation; economic benefits; electric power spot market; flat voltage profile; high prices; multiple distributed capacitor banks; municipal utilities; peak loading reduction; peak shaving; peak usage; power factor correction; reliability benefits; substation voltage reduction; voltage regulation devices; Capacitors; Circuits; Impedance; Power engineering and energy; Power generation economics; Power system economics; Power system reliability; Substations; Systems engineering and theory; Threshold voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Rural Electric Power Conference, 2003
  • Print_ISBN
    0-7803-7905-5
  • Type

    conf

  • DOI
    10.1109/REPCON.2003.1209577
  • Filename
    1209577