Title :
The application of the Equal Area Criterion in ferroresonance
Author :
Heng-xu, Ha ; Hai-quan, Zhou ; Xi-tong, Hu
Author_Institution :
ShanDong Univ. of Technol., Zibo, China
Abstract :
The paper presents a novel technique, a ferroresonance discriminance method of potential transformer, which is adaptive to distinguish whether the system will be excited to be in ferroresonant condition or not, based on time-varying vector analysis method and the Equal Area Criterion. First of all, the time-varying vector mathematical model and IS curve are established according to the zero-mode ferroresonant circuit coming from a typical distribution system. Subsequently, three equilibrium points of the system are all discussed according to the time-varying vector mathematical model and IS curve. Eventually, with the formula definitions of stability margin (Sa) and disturbing quantity (Sdmax) which is according to the IS curve, the ferroresonance discriminance method of potential transformer is established through comparing Sa with Sdmax. Large amounts of ATP simulation tests show that the ferroresonance discriminance method of potential transformer is efficient and accurate.
Keywords :
distribution networks; ferroresonant circuits; potential transformers; time-varying networks; ATP simulation tests; distribution system; disturbing quantity; equal area criteria; ferroresonance discriminance method; ferroresonant circuit; potential transformer; stability margin; time-varying vector analysis method; Analytical models; Ferroresonance; Integrated circuits; 0-mode network; Ferroresonance; disturbing quantity; equal area criterion; equilibrium points; phase-mode transform; stability margin; time-varying vector;
Conference_Titel :
Power System Technology (POWERCON), 2010 International Conference on
Conference_Location :
Hangzhou
Print_ISBN :
978-1-4244-5938-4
DOI :
10.1109/POWERCON.2010.5666382