• DocumentCode
    1610764
  • Title

    Comparison of capacity design of lead-acid battery bank and hybrid energy storage bank for nuclear power plant

  • Author

    Daesik Kim ; Hanju Cha

  • Author_Institution
    Instrum. & Electr. Dept., Korea Inst. of Nucl. Safety, Daejeon, South Korea
  • fYear
    2013
  • Firstpage
    427
  • Lastpage
    431
  • Abstract
    DC power system of the nuclear power plant is used to supply DC loads for engineered safety featured instrumentation and control such as inverter, power system control and indication, and station annunciation [1]. Batteries of DC power system of the nuclear power plant uses lead-acid batteries in present, but new secondary batteries would be installed in nuclear power plant. This paper compares capacity design of lead-acid battery bank and super capacitor battery hybrid energy storage bank, when the battery was connected directly in parallel with the super capacitor. In addition, duty cycle diagram of class 1E DC power system and characteristic of super capacitor battery hybrid energy storage device are analyzed.
  • Keywords
    battery storage plants; energy storage; lead acid batteries; nuclear power stations; DC loads; DC power system; capacity design; duty cycle diagram; hybrid energy storage bank; inverter; lead acid battery bank; nuclear power plant; power system control; Batteries; Capacitors; Hybrid power systems; Power generation; Standards; hybrid energy storage bank; lead acid battery; super capacitor;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Clean Energy and Technology (CEAT), 2013 IEEE Conference on
  • Conference_Location
    Lankgkawi
  • Print_ISBN
    978-1-4799-3237-5
  • Type

    conf

  • DOI
    10.1109/CEAT.2013.6775669
  • Filename
    6775669