DocumentCode :
1612450
Title :
Redesign of a spherical corona shield for UHV substation connectors
Author :
Hernandez-Guiteras, Joan ; Riba Ruiz, Jordi-Roger ; Saavedra, Harold
Author_Institution :
MCIA Res. Group, Univ. Politec. de Catalunya (UPC), Terrassa, Spain
fYear :
2013
Firstpage :
384
Lastpage :
389
Abstract :
When dealing with extra- and ultra-high voltage transmission systems special considerations must be taken into account to minimize corona activity. To minimize its harmful effects often corona shields are required. Depending on the device to protect, corona shields may have different geometries; the most usual are corona caps, toroids and spheres. This work analyzes by means three-dimensional finite elements method simulations the behavior of two spherical shields, i.e. a continuous flat sphere (or standard sphere) and a tubes sphere. Results presented here show that the bar shells allows reducing greatly the weight and ventilates better than the standard solution while ensuring an adequate shielding effect.
Keywords :
corona; finite element analysis; pipes; power transmission protection; shells (structures); substation protection; UHV substation connector; bar shell; continuous flat sphere; extra-high voltage transmission system; geometry; spherical corona shielding effect simulation; three-dimensional finite element method; toroid; tubes sphere; ultrahigh voltage transmission system; Aluminum; Connectors; Corona; Electric fields; Standards; Substations; Wires; corona effect; corona shields; electric field; finite elements method; sphere; substation connector; toroid;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, Energy and Electrical Drives (POWERENG), 2013 Fourth International Conference on
Conference_Location :
Istanbul
ISSN :
2155-5516
Type :
conf
DOI :
10.1109/PowerEng.2013.6635637
Filename :
6635637
Link To Document :
بازگشت