• DocumentCode
    1613578
  • Title

    Transient behavior analysis of Doubly-fed induction generator under unbalanced voltage dips and testing validation

  • Author

    Shao, Wenchang ; Wang, Ruiming ; Li, Qing ; Qin, Shiyao

  • Author_Institution
    China Electr. Power Res. Inst.(CEPRI), Beijing, China
  • fYear
    2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Normally, it´s more difficult to realize Low Voltage Ride through (LVRT) for Doubly-fed induction generator (DFIG) under unbalanced voltage dips than in balanced voltage dips. Unbalanced dips are more harmful to the Doubly-fed induction generator (DFIG) than balanced dips, because they induce higher voltages in the rotor. Besides, the influence of unbalanced grid voltage dips to DFIG is studied together with the transient behavior of DFIG. A theoretical analysis is given to the reasons of the over current occurring during an unbalanced grid voltage dips in this paper. Field testing results with mobile LVRT testing container are also presented to support the analysis.
  • Keywords
    asynchronous generators; power grids; power supply quality; power system transients; rotors; DFIG; LVRT; doubly fed induction generator; low voltage ride through; rotor; transient behavior analysis; unbalanced grid voltage dips; unbalanced voltage dips; Presses; Rotors; DFIG; LVRT; Unbalanced Voltage Dips;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology (POWERCON), 2010 International Conference on
  • Conference_Location
    Hangzhou
  • Print_ISBN
    978-1-4244-5938-4
  • Type

    conf

  • DOI
    10.1109/POWERCON.2010.5666559
  • Filename
    5666559