    Study on the Flashover characteristics of air gaps for San-Hu II ± 500kv double line transmission towers

  • Author

    Yujian, Ding ; Weiming, Liao ; Qingfeng, Li ; Zhaoying, Sun

  • Author_Institution
    China Electr. Power Res. Inst., Beijing, China
  • fYear
    2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Flashover characteristics of the upper frame air gaps for ±500 kV DC double line transmission towers are researched by impulse flashover test on real size simulation tower, and the test curves are presented. Tests about Flashover characteristics impacts of the lower crossbeam on the upper frame air gaps are carried out, the test curves are given in this paper under the precondition that the distance of upper line to upper crossbeam and tower body is 4.4 m and the distance of upper line to lower crossbeam is 2.7 m~4.2 m. Combined with the test result curves when the upper frame gaps have the same distance and the correction formula with different tower width, the curves of lower frame air gaps are also given in this paper. Based on the over-voltage and the switching impulse flashover characteristics on air gaps, the minimum clearances for the air gaps of upper and lower frame of ±500 kV DC double line transmission towers from the Three Gorges Hydropower Station to Shanghai are presented.
  • Keywords
    DC transmission networks; flashover; DC double line transmission tower; Shanghai; Three Gorges Hydropower Station; air gap; size 2.7 m; size 4.4 m; switching impulse flashover; voltage -500 kV; voltage 500 kV; Discharges; Sun; Switches; HVDC transmission line; air clearance; double-circuit transmission line; impulse flashover;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology (POWERCON), 2010 International Conference on
  • Conference_Location
    Hangzhou
  • Print_ISBN
    978-1-4244-5938-4
  • Type

    conf

  • DOI
    10.1109/POWERCON.2010.5666670
  • Filename
    5666670