DocumentCode :
1617905
Title :
Oil and winding temperature control in power transformers
Author :
Dursun, Kamil
Author_Institution :
Ostfold Univ. Coll., Fredrikstad, Norway
fYear :
2013
Firstpage :
1631
Lastpage :
1639
Abstract :
The temperature of oil and paper is crucial in power transformers. In the case of high temperature, the insulation can carbonise and produce gasses, reducing the lifetime of the transformer drastically. One method of effective cooling of windings is to introduce barriers so that the oil flows between discs and not around them as it would do otherwise. This method is well known but an analytical approach would be in place in order to estimate the accurate result of placement of such barriers. In this paper, the Finite Element program COMSOL is used to make such calculations and decide the optimal placement of barriers in a winding. It has been shown that even few barriers reduce the oil and paper temperature significantly. A method to make such calculations is introduced.
Keywords :
cooling; finite element analysis; power transformer insulation; temperature control; transformer oil; transformer windings; COMSOL finite element program; analytical approach; discs; power transformer oil; winding cooling; winding temperature control; Conductivity; Copper; Oil insulation; Power transformer insulation; Thermal conductivity; Windings; Power transformers; hot spots; oil temperature; paper insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, Energy and Electrical Drives (POWERENG), 2013 Fourth International Conference on
Conference_Location :
Istanbul
ISSN :
2155-5516
Type :
conf
DOI :
10.1109/PowerEng.2013.6635861
Filename :
6635861
Link To Document :
بازگشت