DocumentCode :
1620647
Title :
Improvements in protection and commissioning of digital transformer relays at medium voltage industrial facilities
Author :
Mozina, Charles J.
Author_Institution :
Beckwith Electr. Co., Inc., Largo, FL, USA
fYear :
2010
Firstpage :
1
Lastpage :
10
Abstract :
The application of multifunction digital relays to protect medium voltage power transformers has become a common industrial practice. Industrial transformers, unlike utility transformers, frequently use neutral grounding resistors to limit ground current during faults to 200-400A range on medium voltage systems. This paper will discuss why these types of transformers require sensitive ground differential protection. The paper will also discuss the basics of transformer protection including: phasing standards, through-fault withstand capability, differential/fusing/overcurrent protection, slope, CT requirements, harmonic restraint, and communicating these requirements properly when programming and commissioning new digital relays. The rationale for providing transformer overexcitation protection on all major transformers within industrial facilities is also addressed. Advancements in digital technology have allowed relay manufacturers to include more and more relay functions within a single hardware platform as well as address more and more transformer winding configurations. This has resulted in digital transformer relays requiring an Einstein to set and an Edison to commission. Since there are few Einstein´s and Edison´s among us, the next generation of transformer relays needs to concentrate on this complexity issue in addition to technical improvements. This paper addresses these issues that the author believes are the major shortcomings of existing digital transformer protective relays.
Keywords :
earthing; power transformer protection; relay protection; transformer windings; current 200 A to 400 A; differential protection; differential-fusing-overcurrent protection; digital transformer protective relay commissioning; fault withstand capability; ground current; harmonic restraint; medium voltage industrial facility; medium voltage power transformer overexcitation protection; multifunction digital relay programming; neutral grounding resistors; relay functions; relay manufacturers; utility transformer winding; Digital relays; Grounding; Oil insulation; Power transformer insulation; Windings; ANSI; IEC; V/Hz; electro-mechanical relays; harmonic restraint; inrush; low resistance grounding; multifunction digital relay; overexcitation; slope;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference (PCIC), 2010 Record of Conference Papers Industry Applications Society 57th Annual
Conference_Location :
San Antonio, TX
ISSN :
0090-3507
Print_ISBN :
978-1-4244-6800-3
Type :
conf
DOI :
10.1109/PCIC.2010.5666837
Filename :
5666837