DocumentCode :
1620990
Title :
The arc-fault circuit protection
Author :
Parise, G. ; Martirano, L. ; Grasselli, U. ; Benetti, L.
Author_Institution :
Dept. of Electr. Eng., Rome Univ., Italy
Volume :
3
fYear :
2001
Firstpage :
1817
Abstract :
In electrical power systems bolted short-circuits are rare and the fault usually involves arcing and burning; mostly the limit value of minimum short-circuit depends on arcing-fault. In AC low voltage systems, the paper examines the arcing-fault branch circuits as weak points. Different protection measures are available against the arc-faults. A first measure that can guarantee a probabilistic protection is allowed by the adoption of overcurrent protective devices (OCPD), optimizing the design of the structure of the system and/or the coordination of protection. A well known complete protection is allowed by adopting arc-fault circuit interrupters (AFCI) for the protection of branch circuits. The authors suggest a new complete protection allowed wiring of the branch circuits, particularly including extension cords, with special power cables, protected by ordinary ground fault protective devices (GFPD). The suggested design for single-core or multi-core power cables is that each insulated core has a concentric conductor shield. Converting the line-to-line fault into a line to ground fault or into a mixed type is the goal of this special cable type faults ground-forced cable (FGFC).
Keywords :
arcs (electric); cable shielding; earthing; overcurrent protection; power cables; power system faults; power system protection; short-circuit currents; AC low voltage systems; arc-fault circuit interrupters; arc-fault circuit protection; arcing-fault; arcing-fault branch circuits; bolted short-circuits; branch circuits protection; burning; concentric conductor shield; extension cords; faults ground-forced cable; ground fault protective devices; insulated core; line to ground fault; line-to-line fault; minimum short-circuit limit value; multi-core power cables; overcurrent protective devices; power cables; power systems; probabilistic protection; protection coordination; protection measures; single-core power cables; weak points; Cable shielding; Circuit faults; Design optimization; Interrupters; Low voltage; Power cable insulation; Power cables; Power system faults; Power system measurements; Power system protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Conference, 2001. Thirty-Sixth IAS Annual Meeting. Conference Record of the 2001 IEEE
Conference_Location :
Chicago, IL, USA
ISSN :
0197-2618
Print_ISBN :
0-7803-7114-3
Type :
conf
DOI :
10.1109/IAS.2001.955778
Filename :
955778
Link To Document :
بازگشت