• DocumentCode
    1627620
  • Title

    Research of suppressing VFTO for 500kV GIS substation based on EMTP/ATP

  • Author

    ZHuo, Wang ; Weiquan, Wang ; Qiang, Wang

  • Author_Institution
    School of Electric and Information Engineering BeiHua University Jilin Province, China
  • fYear
    2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper introduces very fast transient over-voltage caused by disconnecting switch operation of GIS. ATP-EMTP simulation program is applied to analyze the very fast transient over-voltage of 500kv GIS substation. The effect of protection measures on equipments is compared and analyzed, such as adding opening and closing resistor, R-C absorber, and Ferrite Rings. Also the measures are analyzed with considering the actual situation. This research thinking takes safety and economy into account, which can provide new reference for the engineering.
  • Keywords
    Capacitance; Ferrites; Geographic Information Systems; Integrated circuit modeling; Power transformer insulation; Resistors; Surges; ATP-EMTP; GIS substation; VFTO; over-voltage; protection measures;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    E -Business and E -Government (ICEE), 2011 International Conference on
  • Conference_Location
    Shanghai, China
  • Print_ISBN
    978-1-4244-8691-5
  • Type

    conf

  • DOI
    10.1109/ICEBEG.2011.5881357
  • Filename
    5881357