DocumentCode
162874
Title
A modified CIGRE HVDC benchmark model for 60 Hz applications
Author
Schwartz, Justin ; Rahimi, Ebrahim ; Zareipour, Hamidreza
Author_Institution
AltaLink Manage. Ltd., Calgary, AB, Canada
fYear
2014
fDate
7-9 Sept. 2014
Firstpage
1
Lastpage
6
Abstract
This paper proposes a 60 Hz equivalent to the CIGRE benchmark model (CBM) for HVDC control studies. Component configuration and system impedances of the PSCAD/EMTDC implementation of the CBM are modified to arrive at the 60 Hz equivalent model. These parameter changes are discussed and validation is given. Simulations are conducted in steady state and compared to that of the CBM. The response of the proposed equivalent to a current order step-response and AC faults are compared to that of the CBM. The performance comparisons match closely and this paper concludes that the proposed 60 Hz equivalent is adequate for use when running simulations that require an HVDC benchmark model be connected to a representation of a 60 Hz AC network.
Keywords
HVDC power convertors; HVDC power transmission; control engineering computing; power system CAD; power transmission control; AC faults; CBM; EMTDC implementation; HVDC control studies; PSCAD implementation; component configuration; current order step-response; frequency 60 Hz; modified CIGRE benchmark model; system impedances; Current measurement; HVDC transmission; Harmonic analysis; Impedance; Inverters; Rectifiers; Steady-state;
fLanguage
English
Publisher
ieee
Conference_Titel
North American Power Symposium (NAPS), 2014
Conference_Location
Pullman, WA
Type
conf
DOI
10.1109/NAPS.2014.6965411
Filename
6965411
Link To Document