    Zero sequence circuit of three-legged core type transformers

  • Author

    Wang, Jialong ; Lascu, Raluca

  • Author_Institution
    Basler Electr., Highland, IL
  • fYear
    2009
  • Firstpage
    188
  • Lastpage
    213
  • Abstract
    For three-legged Y-YG core type transformers, due to the high reluctance of zero-sequence magnetic return path, the zero-sequence magnetizing impedance is low. The low zero-sequence magnetizing impedance will allow fault current to flow for a line-ground fault in the YG side of a three-legged core type transformer. When calculating line-ground fault current of a three-legged core type transformer, the zero sequence equivalent circuit needs to include the zero-sequence magnetizing impedance. The zero-sequence equivalent circuit from most classic reference books does not take magnetizing impedance into account and needs to be modified. This paper gives the modified zero-sequence equivalent circuit for a three-legged core-type transformer. Theoretical calculation, computer simulation, and actual staged tests verify that fault current based on the modified zero sequence circuit matches the result from the simulation and actual test.
  • Keywords
    fault currents; power transformers; transformer cores; line-ground fault current; magnetizing impedance; three-legged core type transformer; zero sequence circuit; Books; Circuit faults; Circuit testing; Computational modeling; Computer simulation; Equivalent circuits; Fault currents; Impedance; Magnetic cores; Transformer cores;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2009 62nd Annual Conference for
  • Conference_Location
    Austin, TX
  • Print_ISBN
    978-1-4244-4182-2
  • Electronic_ISBN
    978-1-4244-4183-9
  • Type

    conf

  • DOI
    10.1109/CPRE.2009.4982513
  • Filename
    4982513