Title :
Zero sequence circuit of three-legged core type transformers
Author :
Wang, Jialong ; Lascu, Raluca
Author_Institution :
Basler Electr., Highland, IL
Abstract :
For three-legged Y-YG core type transformers, due to the high reluctance of zero-sequence magnetic return path, the zero-sequence magnetizing impedance is low. The low zero-sequence magnetizing impedance will allow fault current to flow for a line-ground fault in the YG side of a three-legged core type transformer. When calculating line-ground fault current of a three-legged core type transformer, the zero sequence equivalent circuit needs to include the zero-sequence magnetizing impedance. The zero-sequence equivalent circuit from most classic reference books does not take magnetizing impedance into account and needs to be modified. This paper gives the modified zero-sequence equivalent circuit for a three-legged core-type transformer. Theoretical calculation, computer simulation, and actual staged tests verify that fault current based on the modified zero sequence circuit matches the result from the simulation and actual test.
Keywords :
fault currents; power transformers; transformer cores; line-ground fault current; magnetizing impedance; three-legged core type transformer; zero sequence circuit; Books; Circuit faults; Circuit testing; Computational modeling; Computer simulation; Equivalent circuits; Fault currents; Impedance; Magnetic cores; Transformer cores;
Conference_Titel :
Protective Relay Engineers, 2009 62nd Annual Conference for
Conference_Location :
Austin, TX
Print_ISBN :
978-1-4244-4182-2
Electronic_ISBN :
978-1-4244-4183-9
DOI :
10.1109/CPRE.2009.4982513