Protecting transmission lines terminated into transformers
Author
Price, Elmo ; Hedding, Roger
Author_Institution
ABB Inc., Norwalk, CT
fYear
2009
Firstpage
276
Lastpage
287
Abstract
Transmission lines that are terminated into transformers are applications where the line and transformer cannot be separated by a circuit breaker and are therefore in the same zone of protection. These applications may be addressed with either current differential or line distance protection. In either case the implementation of separate transformer differential protection isolating the protection zone is recommended. The line protection application needs to consider the instrument transformer locations and transformer winding connections at the transformer end. This paper will discuss the application considerations for both line differential and distance schemes for lines terminated into transformers and provide application guidelines.
Keywords
instrument transformers; power transformer protection; power transmission lines; power transmission protection; transformer windings; circuit breaker; instrument transformer location; transformer winding; transmission line protection; Circuit breakers; Circuit faults; Distributed parameter circuits; Impedance; Instrument transformers; Power transformers; Power transmission lines; Protection; Protective relaying; Transmission lines; Protection; transformers; transmission lines;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2009 62nd Annual Conference for
Conference_Location
Austin, TX
Print_ISBN
978-1-4244-4182-2
Electronic_ISBN
978-1-4244-4183-9
Type
conf
DOI
10.1109/CPRE.2009.4982519
Filename
4982519
Link To Document