DocumentCode :
1633052
Title :
Bus protection for impedance grounded systems
Author :
Hunt, Rich
Author_Institution :
GE Digital Energy, ON
fYear :
2009
Firstpage :
426
Lastpage :
450
Abstract :
It is common for the electrical distribution systems in industrial facilities to be grounded through an impedance. Impedance grounded systems are either high-resistance grounded or low- resistance grounded. High-resistance grounding typically limits the ground fault current between 2A to 5A. Low-resistance grounding system typically limits the ground fault current between 200A and 500A. In either case, the goal is to limit the equipment damage caused by ground faults, while still having enough current for sensitive relays to detect and clear ground faults.
Keywords :
earthing; fault diagnosis; power distribution protection; relay protection; bus protection; electrical distribution systems; ground fault current; high-resistance grounding; impedance grounded systems; industrial facilities; low-resistance grounding; Circuit faults; Fault currents; Grounding; Hazards; Impedance; Industrial plants; Protection; Protective relaying; Relays; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2009 62nd Annual Conference for
Conference_Location :
Austin, TX
Print_ISBN :
978-1-4244-4182-2
Electronic_ISBN :
978-1-4244-4183-9
Type :
conf
DOI :
10.1109/CPRE.2009.4982531
Filename :
4982531
Link To Document :
بازگشت