Title :
Comparison between high impedance and low impedance bus differential protection
Author :
Holbach, Juergen
Author_Institution :
Siemens Energy, Inc., Raleigh, NC
Abstract :
High impedance bus differential relays are used on most of the busses in North America. The popularity can be explained by the good performance of this scheme in relation to CT saturation and the low cost, if used on a simple bus system. However with the introduction of numerical relays and their low CT burden as well as their ability of measuring several feeder currents, a low impedance bus differential principal could be applied on simple busses also. In addition, the availability of fiber optic communication inside of the substation allows the use of decentralized bus system in which the CT output values becomes transmitted via communication to a centralized unit versus having CT wires running to the control house. Low impedance bus differential protection systems have many positive attributes. Common advantages of all low impedance bus protection schemes are the ability to be able to use CT´s of different ratios on respective branch inputs and the fact that the same CT used for the bus protection can be shared with the feeder protection relay. The question needs to be discussed what selection criteria needs to get evaluated for the selection of the appropriate principal.
Keywords :
field buses; relay protection; CT saturation; North America busses; decentralized bus system; feeder currents; high-low impedance bus differential relay protection; low impedance bus differential protection systems; Circuit faults; Costs; Current measurement; Fault currents; Impedance measurement; North America; Optical fiber communication; Protective relaying; Substation protection; Wires;
Conference_Titel :
Protective Relay Engineers, 2009 62nd Annual Conference for
Conference_Location :
Austin, TX
Print_ISBN :
978-1-4244-4182-2
Electronic_ISBN :
978-1-4244-4183-9
DOI :
10.1109/CPRE.2009.4982541