• DocumentCode
    164383
  • Title

    Powerline earthing design in compliance with the latest Australian Standard on Overhead Lines, AS/NZS 7000:2010

  • Author

    Mohseni, Masoumeh

  • fYear
    2014
  • fDate
    Sept. 28 2014-Oct. 1 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents a powerline earthing assessment carried out based upon the latest Australian Standard on Overhead Lines, AS/NZS 7000:2010. The 33kV powerline under study supplies a mining process plant spread over a relatively large geographical area. A number of on-site soil resistivity tests have been undertaken to identify the electrical characteristics of the local soil, followed by network analysis in DIgSILENT PowerFactory to obtain the most onerous earth fault parameters. Safety step and touch voltage limits are obtained in accordance to AS/NZS 7000. Finally detailed modelling analysis in CDEGS software package investigates the most economically efficient earthing design that complies with the safety voltage criteria obtained from AS/NZS 7000.
  • Keywords
    earthing; power cables; power overhead lines; risk analysis; AS/NZS 7000:2010; Australian Standard on Overhead Lines; earth fault parameters; mining process plant; network analysis; on site soil resistivity tests; powerline earthing design; safety step; touch voltage limits; Conductivity; Earth; Educational institutions; Grounding; Hazards; Soil; Powerline; earthing design; risk management;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Conference (AUPEC), 2014 Australasian Universities
  • Conference_Location
    Perth, WA
  • Type

    conf

  • DOI
    10.1109/AUPEC.2014.6966583
  • Filename
    6966583