DocumentCode
1643840
Title
Condition monitoring of power transformers in the Australian State of New South Wales using transfer function measurements
Author
Stace, Mark ; Islam, Syed M.
Author_Institution
Electr. Plant Testing, Australia
Volume
1
fYear
1997
Firstpage
248
Abstract
A Power transformer is a critical unit within a power network. A large transformer failure could cause long interruptions and costly repairs. Therefore, it is desirable to detect potential failures as early as possible. Model based diagnosis such as the transfer function method is becoming increasingly popular in transformer condition monitoring. The transfer function method is particularly useful in identifying faults such as winding deformation and displacement, inter-turn and inter-disc faults. In this paper, practical experiences in transfer function measurements on four identical 132/66/11 kV 30 MVA power transformers has been presented
Keywords
power system measurement; power transformer testing; transfer functions; 30 MVA; New South Wales; condition monitoring; failure; inter-disc fault; inter-turn fault; model based diagnosis; power transformer; transfer function measurement; winding deformation; winding displacement; Australia; Capacitance; Circuit faults; Condition monitoring; Fault diagnosis; Power measurement; Power transformers; Resonant frequency; Testing; Transfer functions;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1997., Proceedings of the 5th International Conference on
Conference_Location
Seoul
Print_ISBN
0-7803-2651-2
Type
conf
DOI
10.1109/ICPADM.1997.617574
Filename
617574
Link To Document