  • Abstract
    A Power transformer is a critical unit within a power network. A large transformer failure could cause long interruptions and costly repairs. Therefore, it is desirable to detect potential failures as early as possible. Model based diagnosis such as the transfer function method is becoming increasingly popular in transformer condition monitoring. The transfer function method is particularly useful in identifying faults such as winding deformation and displacement, inter-turn and inter-disc faults. In this paper, practical experiences in transfer function measurements on four identical 132/66/11 kV 30 MVA power transformers has been presented
  • Keywords
    power system measurement; power transformer testing; transfer functions; 30 MVA; New South Wales; condition monitoring; failure; inter-disc fault; inter-turn fault; model based diagnosis; power transformer; transfer function measurement; winding deformation; winding displacement; Australia; Capacitance; Circuit faults; Condition monitoring; Fault diagnosis; Power measurement; Power transformers; Resonant frequency; Testing; Transfer functions;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1997., Proceedings of the 5th International Conference on
  • Conference_Location
    Seoul
  • Print_ISBN
    0-7803-2651-2
  • Type

    conf

  • DOI
    10.1109/ICPADM.1997.617574
  • Filename
    617574