DocumentCode :
164535
Title :
Auto-cross correlation coefficients used for detecting an internal fault in three phase transformer
Author :
Etumi, A.A. ; Anayi, F.J. ; Fahmy, Aly A. ; Eldukhri, E.E.
Author_Institution :
Sch. of Eng., Cardiff Univ., Cardiff, UK
fYear :
2014
fDate :
25-28 May 2014
Firstpage :
370
Lastpage :
374
Abstract :
A new algorithm based on correlation coefficients analysis of waveforms to detect an internal fault occurs in three phase transformer is proposed. The algorithm depends on the changes in current waveform that occur during internal fault. Auto-correlation has been added to cross-correlation algorithm for enhancing the security and speed in detecting the fault within very short time. It is able to detect the fault after just 0.4 msec from incidence of fault occurrence. The scheme has been tested by using Matlab/Simulink software [1]. The test results show that the internal fault even inter-turn type can be correctly identified from external fault. The algorithm is simple and can be experimentally implemented.
Keywords :
fault diagnosis; power transformers; Matlab/Simulink software; correlation coefficients analysis; cross-correlation algorithm; external fault; internal fault detection; three phase transformer; Circuit faults; Correlation coefficient; Current transformers; Mathematical model; Monitoring; Power transformers; Relays; Improved correlation technique; Matlab/Simulink software; external fault; internal fault; transformer differential protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location :
Bucharest
Type :
conf
DOI :
10.1109/ICHQP.2014.6842784
Filename :
6842784