• DocumentCode
    1646
  • Title

    On-line PD detection and localization in cross-bonded HV cable systems

  • Author

    Bojie Sheng ; Wenjun Zhou ; Jianhui Yu ; Shaoxin Meng ; Chengke Zhou ; Hepburn, Donald M.

  • Author_Institution
    Sch. of Electr. Eng., Wuhan Univ., Wuhan, China
  • Volume
    21
  • Issue
    5
  • fYear
    2014
  • fDate
    Oct. 2014
  • Firstpage
    2217
  • Lastpage
    2224
  • Abstract
    This paper addresses the detection and localization of partial discharge (PD) in crossbonded (CB) high voltage (HV) cables. A great deal has been published in recent years on PD based cable insulation condition monitoring, diagnostics and localization in medium voltage (MV) and high voltage (HV) cables. The topic of pulse propagation and PD source localization in CB HV cable systems has yet to be significantly investigated. The main challenge to PD monitoring of CB HV cables is as a result of the interconnectedness of the sheaths of the three single phase cables. The cross-bonding of the sheaths makes it difficult to localize which of the three phases a PD signal has emanated from. Co-axial cables are used to connect cable sheaths to cable link boxes, for ease of installation and protection against moisture. A second challenge is, therefore, the coupling effect when a PD pulse propagates in HV cable joints and the co-axial cables, making PD detection and localization more complex. The paper presents experimental investigations into PD pulse coupling between the cable center conductor and the sheath and the behavior of PD pulse propagation in CB HV cables. It proposes a model to describe PD pulse propagation in a CB HV cable system to allow monitoring and localization, and also presents the knowledge rules required for PD localization in CB HV cable systems.
  • Keywords
    cable sheathing; coaxial cables; partial discharge measurement; CB HV cable systems; PD pulse coupling; PD pulse propagation; PD signal; PD source localization; cable center conductor; cable sheaths; coaxial cables; cross-bonded HV cable systems; high voltage cables; medium voltage cables; on-line PD detection; on-line PD localization; partial discharge; Cable insulation; Cable shielding; Coaxial cables; Conductors; Couplings; Partial discharges; Power cables; Cable; PD localization; coupling effect; cross-bonding; on-line insulation condition monitoring; partial discharge;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004446
  • Filename