Title :
Comparison of active crowbar protection schemes for DFIGs wind turbines
Author :
Sava, Gabriela Nicoleta ; Costinas, Sorina ; Golovanov, Nicolae ; Leva, S. ; Quan, Duong Minh
Author_Institution :
Fac. of Power Eng., Univ. Politeh. of Bucharest, Bucharest, Romania
Abstract :
The doubly fed induction generators (DFIGs) are used in almost 50% of the offshore and onshore wind power plants. The DFIGs offer advantages compared to fix speed induction generators. The DFIGs are sensitive to grid voltage disturbances and require additional protection for the rotor side power electronic converter, like crowbar protection. In the present paper two active crowbar topologies are compared, IGBT with bypass resistor and rectifier with IGBT, which were the most studied in the scientific literature. A DFIG model with analyzed crowbar protections was implemented in Matlab/Simulink. The simulation results reveal that both solutions can limit the rotor current and the dc link voltage values. However, the solution with rectifier offers better results.
Keywords :
asynchronous generators; offshore installations; power convertors; power grids; rectifiers; resistors; rotors; topology; wind turbines; DFIG wind turbines; IGBT; active crowbar protection schemes; active crowbar topologies; bypass resistor; dc link voltage values; doubly fed induction generators; grid voltage disturbances; offshore wind power plants; onshore wind power plants; rectifier; rotor side power electronic converter; Induction generators; Insulated gate bipolar transistors; Reactive power; Resistance; Rotors; Stators; Wind turbines; DC voltage; crowbar protection; rotor current; short circuit; wind power plant;
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location :
Bucharest
DOI :
10.1109/ICHQP.2014.6842860