• DocumentCode
    164662
  • Title

    Evaluation of voltage dip severity based on lost voltage-time area

  • Author

    Farkas, Csaba ; Dan, Andras

  • Author_Institution
    Dept. of Electr. Power Eng., BUTE, Budapest, Hungary
  • fYear
    2014
  • fDate
    25-28 May 2014
  • Firstpage
    521
  • Lastpage
    525
  • Abstract
    Nowadays, the ITIC curve is commonly used for evaluating voltage dips´ severity. However, this curve may not catch equipment sensitivity well enough and it certainly lacks the information about the probability of whether any equipment is indeed switched on or not. In this paper we present a novel voltage dip severity evaluation method based on the lost voltage-time area of the dip and also give detailed insight into the generalization of this method based on fuzzy logic. To compare the different methods used in the industry, the ones found in the literature and ours with each other, a voltage dip evaluator program was written in MATLAB and the methods were tested against each other by using voltage dip measurement data received from the local DSO. The probability of whether any equipment is switched on or not is also investigated by using a so-called on-period curve that was determined by taking average household consumption data into consideration.
  • Keywords
    fuzzy logic; power apparatus; power supply quality; probability; DSO; ITIC curve; equipment sensitivity; fuzzy logic; household consumption data; lost voltage-time area; voltage dip evaluator program; voltage dip measurement data; voltage dip severity evaluation method; Power quality; Sensitivity; Standards; Threshold voltage; Voltage fluctuations; Voltage measurement; ITIC; power quality; voltage dip; voltage-time area;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
  • Conference_Location
    Bucharest
  • Type

    conf

  • DOI
    10.1109/ICHQP.2014.6842868
  • Filename
    6842868