DocumentCode
1649329
Title
Float charging of valve regulated lead acid batteries-gel telecom batteries with integrated monitoring
Author
Rusch, Wieland ; Göbel, Stefan ; Lütkehölter, Reinhard
Author_Institution
VARTA Batterie AG, Hagen, Germany
fYear
1995
Firstpage
632
Lastpage
636
Abstract
VARTA has investigated the float charging of VRLA batteries under various charging and environmental conditions. We found out that under special conditions one of the electrodes is continuously discharged although the cell is on float charge with 2.23 V. To get a complete picture we derived the kinetic parameters of the relevant reactions and developed a mathematical model. With this model we can give guide lines for the appropriate design and can define the proper operating conditions for VRLA-batteries. The monitoring of telecom batteries is to our understanding an integral part of the battery manufacturers scope of supply. Clear responsibility, correct analysis of the battery condition at site and immediate action if necessary count for it. The authors briefly describe the reaction model, the kinetic parameters, and integrated battery monitoring with the VARTA multilogic system
Keywords
computerised monitoring; lead; monitoring; reaction kinetics; secondary cells; telecommunication power supplies; Pb; Pb acid batteries; VARTA; VARTA multilogic system; environmental conditions; float charging; gel telecom batteries; integrated monitoring; kinetic parameters; reaction model; valve regulated lead acid batteries; Batteries; Corrosion; Electrodes; Hydrogen; Lead; Manufacturing; Oxygen; Telecommunications; Valves; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1995. INTELEC '95., 17th International
Conference_Location
The Hague
Print_ISBN
0-7803-2750-0
Type
conf
DOI
10.1109/INTLEC.1995.499023
Filename
499023
Link To Document