• DocumentCode
    1649329
  • Title

    Float charging of valve regulated lead acid batteries-gel telecom batteries with integrated monitoring

  • Author

    Rusch, Wieland ; Göbel, Stefan ; Lütkehölter, Reinhard

  • Author_Institution
    VARTA Batterie AG, Hagen, Germany
  • fYear
    1995
  • Firstpage
    632
  • Lastpage
    636
  • Abstract
    VARTA has investigated the float charging of VRLA batteries under various charging and environmental conditions. We found out that under special conditions one of the electrodes is continuously discharged although the cell is on float charge with 2.23 V. To get a complete picture we derived the kinetic parameters of the relevant reactions and developed a mathematical model. With this model we can give guide lines for the appropriate design and can define the proper operating conditions for VRLA-batteries. The monitoring of telecom batteries is to our understanding an integral part of the battery manufacturers scope of supply. Clear responsibility, correct analysis of the battery condition at site and immediate action if necessary count for it. The authors briefly describe the reaction model, the kinetic parameters, and integrated battery monitoring with the VARTA multilogic system
  • Keywords
    computerised monitoring; lead; monitoring; reaction kinetics; secondary cells; telecommunication power supplies; Pb; Pb acid batteries; VARTA; VARTA multilogic system; environmental conditions; float charging; gel telecom batteries; integrated monitoring; kinetic parameters; reaction model; valve regulated lead acid batteries; Batteries; Corrosion; Electrodes; Hydrogen; Lead; Manufacturing; Oxygen; Telecommunications; Valves; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1995. INTELEC '95., 17th International
  • Conference_Location
    The Hague
  • Print_ISBN
    0-7803-2750-0
  • Type

    conf

  • DOI
    10.1109/INTLEC.1995.499023
  • Filename
    499023