Title :
Equipment failures caused by power quality disturbances
Author :
Bendre, Ashish ; Divan, Deepak ; Kranz, William ; Brumsickle, William
Author_Institution :
DRS Power & Control Technol., Milwaukee, WI, USA
Abstract :
This paper provides insight into a failure mechanism that impacts a broad range of industrial equipment. Voltage surges have often been blamed for unexplained equipment failure in the field. Extensive voltage monitoring data suggests that voltage sags occur much more frequently than voltage surges, and that current surges that accompany voltage sag recovery may be the actual culprit causing equipment damage. A serious limitation in equipment specification is highlighted, pointing to what is possibly the root-cause for a large percentage of unexplained equipment field failures. This paper also outlines the need for a standard governing the behavior of equipment under voltage sags, and suggests solutions to protect existing equipment in the field.
Keywords :
fault location; power supply quality; power system measurement; surges; equipment failures; industrial equipment; power quality disturbances; voltage monitoring; voltage sag recovery; voltage surges; Equipment failure; Failure analysis; Industrial control; Lightning; Power quality; Power system stability; Process control; Production facilities; Surge protection; Voltage fluctuations;
Conference_Titel :
Industry Applications Conference, 2004. 39th IAS Annual Meeting. Conference Record of the 2004 IEEE
Print_ISBN :
0-7803-8486-5
DOI :
10.1109/IAS.2004.1348450