Case studies on electromagnetic interference between HVPL and buried pipelines
Author :
Stet, Denisa ; Micu, Dan D. ; Czumbil, Levente ; Manea, Bogdan
Author_Institution :
Dept. of Electrotehnics & Meas., Tech. Univ. of Cluj-Napoca, Cluj-Napoca, Romania
fYear :
2014
fDate :
16-18 Oct. 2014
Firstpage :
231
Lastpage :
236
Abstract :
Electromagnetic interferences between an existing gas pipeline and a newly designed high voltage power line sharing the same right-of-way, are evaluated. Induced voltages are computed for different steady state power line operating conditions, using dedicated professional software. To increase results accuracy, soil resistivity measurements were made along distribution corridor length and the appropriate equivalent soil model is determined. Obtained induced AC voltages values are compared to international regulation for identification of potentially hazardous zones regarding pipeline corrosion. Different mitigation techniques are tested and proposed.
Keywords :
electric resistance measurement; electromagnetic interference; pipelines; power transmission lines; soil; terrestrial electricity; appropriate equivalent soil model; distribution corridor length; electromagnetic interferences; gas pipeline; high voltage power line; induced AC voltages values; pipeline corrosion; right-of-way; soil resistivity measurements; steady state power line operating conditions; Conductivity; Interference; Joints; Pipelines; Soil; Voltage measurement; Wires; AC induced voltages; electromagnetic interferences; mitigation technique; underground pipeline;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical and Power Engineering (EPE), 2014 International Conference and Exposition on
Conference_Location :
Iasi
Type :
conf
DOI :
10.1109/ICEPE.2014.6969903
Filename :
6969903
Link To Document :
بازگشت