DocumentCode
1677941
Title
Partial discharge mapping in high voltage (HV) cable networks
Author
Shim, I. ; Soraghan, JJ ; Siew, WH ; McPherson, F. ; Sludden, K. ; Gale, PF
Author_Institution
Dept. of Electron. & Electr. Eng., Strathclyde Univ., Glasgow, UK
fYear
1999
fDate
6/21/1905 12:00:00 AM
Firstpage
497
Lastpage
500
Abstract
This paper presents a new technique for locating partial discharges in HV cables. The method has been developed and used for on-line measurement of HV cable networks. When there is more than one PD site, the PD location procedure becomes intricate. The PD patterns are processed to detect the individual PD locations. An analogue model was built to verify and test the technique proposed. The results of the PD generated from the model are presented and discussed. Real data from the field are later compared to the results obtained from the model
Keywords
fault location; insulation testing; partial discharge measurement; power cable insulation; power cable testing; HV cables; PD location procedure; PD site; analogue model; high voltage cable networks; on-line measurement; partial discharge mapping; partial discharges location; Breakdown voltage; Communication cables; Fault location; Intelligent networks; Oscilloscopes; Partial discharges; Programmable control; Pulse measurements; Testing; Timing;
fLanguage
English