Abstract :
Two aspects of a process identification related to the model accuracy and process identifiability are discussed. The identification is used on a first stage of controller tuning, while the second stage is a controller parameter optimization. A restriction on identified model bandwidth is determined for controller parameter optimization from the correct tuning point of view. Besides, the requirement for a deterministic test signal is formulated from a process identifiability point of view in the case of the nonparametric identification. Retrofit of two 75 MW boilers at IEC Power Station is fulfilled by implementation of this tuning procedure, yielding satisfactory results
Keywords :
boilers; identification; optimal control; power station control; steam power stations; tuning; 75 MW; IEC Power Station; Israel Electric Corporation; controller parameter optimization; deterministic test signal; identified model bandwidth; model accuracy; nonparametric identification; optimal tuning; power boiler control loops; process identifiability; process identification; Boilers; Control systems; Delay effects; Frequency estimation; Frequency response; Fuels; Optimal control; Pressure control; Temperature control; Transfer functions;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrotechnical Conference, 1998. MELECON 98., 9th Mediterranean
Conference_Location :
Tel-Aviv
Print_ISBN :
0-7803-3879-0
Type :
conf
DOI :
10.1109/MELCON.1998.692473
Filename :
692473
Link To Document :
بازگشت