DocumentCode :
1684628
Title :
Calculation of circuit breaker transient recovery voltages
Author :
Tran-Quoc, T. ; Lam-Du, S. ; Feuillet, R. ; Sabonnadiere, J.C.
Author_Institution :
Lab. d´´Electrotech. de Grenoble, St. Martin d´´Heres, France
fYear :
1999
Firstpage :
242
Abstract :
This paper investigates the calculation of circuit breaker transient recovery voltages for the Vietnam 500 kV power system. Several events that can produce high transient recovery voltage levels on the 500 kV line breakers are studied, such as three-phase-to-ground, phase-to-phase grounded, phase-to-phase ungrounded and phase-to-ground fault clearing. The series capacitors protected by varistors, used on the Vietnam 500 kV system, play an important role to increase the TRVs across line circuit breakers when clearing fault currents. The influence of fault location on TRV is investigated. Several measures in order to reduce the TRVs are examined.
Keywords :
circuit breakers; power capacitors; power system faults; power system transients; 500 kV; Vietnam; circuit breaker transient recovery voltages; phase-to-ground fault clearing; phase-to-phase grounded fault clearing; phase-to-phase ungrounded fault clearing; power system; series capacitors; three-phase-to-ground fault clearing; varistors; Capacitors; Circuit breakers; Circuit faults; Fault currents; Power system faults; Power system protection; Power system transients; Transient analysis; Varistors; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
Conference_Location :
Budapest, Hungary
Print_ISBN :
0-7803-5836-8
Type :
conf
DOI :
10.1109/PTC.1999.826674
Filename :
826674