• DocumentCode
    1685350
  • Title

    Voltage sag analysis and solution for an industrial plant with embedded induction motors

  • Author

    Felce, Angel ; Matas, Guillermo ; Da Silva, Ysmael

  • Author_Institution
    Inelectra S.A.C.A, Caracas, Venezuela
  • Volume
    4
  • fYear
    2004
  • Firstpage
    2573
  • Abstract
    In This work a power quality (PQ) problem in an industrial plant is analyzed and its possible solutions explored, specifically regarding voltage sags. It is analyzed a plant\´s electrical system sensitivity regarding voltage sags, how does the magnitude depression and its duration affect the performance of the electrical loads (mainly induction motors). Several proposals are discussed and explored for voltage sag mitigation and their feasibility for the plant\´s PQ problem. Finally, settings of the voltage sag mitigation equipment (timer or "latching" relay) are made analyzing voltage recovery times after voltage sag has occurred.
  • Keywords
    induction motors; industrial plants; load (electric); power supply quality; electrical load; embedded induction motors; industrial plant; plant electrical system; relay; voltage recovery; voltage sag analysis; voltage sag mitigation equipment; Costs; Electricity supply industry; Induction motors; Industrial plants; Performance analysis; Power quality; Power system relaying; Proposals; Threshold voltage; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2004. 39th IAS Annual Meeting. Conference Record of the 2004 IEEE
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-8486-5
  • Type

    conf

  • DOI
    10.1109/IAS.2004.1348838
  • Filename
    1348838