• DocumentCode
    1689569
  • Title

    Improved EHV line switching surge control by application of MO-arresters and controlled switching

  • Author

    Carvalho, A. ; Lacorte, M. ; Knudsen, O.

  • Author_Institution
    ABB High Voltage Technol. Ltd., Zurich-Oerlikon, Switzerland
  • Volume
    1
  • fYear
    1995
  • Firstpage
    292
  • Abstract
    Transmission line switching surges and its limitation by means of metal-oxide (MO) surge arresters and controlled switching are discussed. The benefits of these overvoltage control methods are analysed based on extensive simulation studies of 550 kV transmission lines. The line length is taken as an independent parameter and the degree of shunt-compensation is considered as well. The simulation studies show that MO arresters and controlled switching cope in most cases with the insulation coordination requirements of 550 kV networks, thus eliminating the need of closing resistors
  • Keywords
    arresters; compensation; insulation co-ordination; overvoltage protection; power system control; power transmission lines; switching; voltage control; 550 kV; EHV line switching surge control; closing resistors; controlled switching; insulation coordination requirements; metal oxide arresters; overvoltage control methods; shunt-compensation; Arresters; Distributed parameter circuits; Insulation; Power system protection; Power system simulation; Power transmission lines; Resistors; Surge protection; Switching circuits; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Management and Power Delivery, 1995. Proceedings of EMPD '95., 1995 International Conference on
  • Print_ISBN
    0-7803-2981-3
  • Type

    conf

  • DOI
    10.1109/EMPD.1995.500741
  • Filename
    500741