Title :
Influence of reactors on input harmonics of variable frequency drives
Author :
Liang, Xiaodong ; Ilochonwu, Obinna ; Lim, Jeffrey
Author_Institution :
Edmonton Product Center, Schlumberger, Edmonton, AB, Canada
Abstract :
AC line reactors and DC link reactors are widely used in variable frequency drives (VFDs) to improve the drive performance such as reducing input harmonics, improving the input power factor, and protecting the drives from surges etc. The effectiveness of both types of reactors in reducing input harmonics is affected by many factors, including the loading of the drives and the system source impedance. In this paper, a simulation is conducted to investigate the influence of such factors. An onshore and offshore power distribution systems with VFDs as the dominant loads are used as the case studies. The rules to evaluate needs for AC line or DC link reactors are proposed for practical applications.
Keywords :
distribution networks; power system harmonics; reactors (electric); variable speed drives; AC line reactors; DC link reactors; dominant loads; drive performance; input harmonics; input power factor; offshore power distribution systems; onshore power distribution systems; system source impedance; variable frequency drives; Harmonic analysis; Impedance; Inductance; Inductors; Loading; Power harmonic filters; AC line reactor; DC link reactor; input harmonics; power source impedance; variable frequency drives;
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference (I&CPS), 2011 IEEE
Conference_Location :
Baltimore, MD
Print_ISBN :
978-1-4244-9999-1
DOI :
10.1109/ICPS.2011.5890883