DocumentCode
1694984
Title
Positive feedback stabilization of compressor surge
Author
Willems, Frank ; Heemels, Maurice ; De Jager, Bram ; Stoorvogel, Anton
Author_Institution
Eindhoven Univ. of Technol., Netherlands
Volume
4
fYear
1999
fDate
6/21/1905 12:00:00 AM
Firstpage
3259
Abstract
Stable operation of axial and centrifugal compressors is limited towards low mass flows due to the onset of surge. The stable operating region can be enlarged by active control. In this study, we use a control valve which is nominally closed and only opens to stabilize the system around the desired operating point. Hence, only non-negative control values are allowed which complicates the controller design considerably. A novel positive feedback controller is proposed with clear design parameters to obtain a desirable closed loop behavior. The technique has successfully been applied to a compression system model. For arbitrarily large control valve capacities, the system can be stabilized in the entire operating region. Simulations show that the surge point mass flow can be reduced up to 15% for the relatively small control valve to be implemented on the actual installation. Using this efficient control strategy, the stabilized operating point is reached with zero control valve mass flow
Keywords
closed loop systems; compressors; feedback; flow control; stability; transient response; valves; closed loop systems; compressors; control valve; mass flow control; positive feedback; stabilization; surge point; Chemical industry; Control systems; Feedback; Open loop systems; Pressure control; Stability; Surges; Turbines; Valves; Weight control;
fLanguage
English
Publisher
ieee
Conference_Titel
Decision and Control, 1999. Proceedings of the 38th IEEE Conference on
Conference_Location
Phoenix, AZ
ISSN
0191-2216
Print_ISBN
0-7803-5250-5
Type
conf
DOI
10.1109/CDC.1999.827773
Filename
827773
Link To Document