DocumentCode :
1695668
Title :
Distribution line automation system based on non-communication protection in the case of symmetrical fault
Author :
Yin Diqing ; Liu Kun ; Dong Xinzhou ; Shi Shenxing ; Xu Gang ; Wang Kai
Author_Institution :
North City Branch of Shanghai Power Co., Shanghai, China
Volume :
1
fYear :
2011
Firstpage :
659
Lastpage :
662
Abstract :
Distribution line non-communication protection (DNCP) can quickly and selectively isolate unsymmetrical fault, but the performance of this distribution line automation system is not satisfying in the case of symmetrical fault. This paper proposes a scheme which can quickly isolate symmetrical fault and block the operation of BPS: DNCP which is closed to the source can operate instantaneously, that can avoid overheating damage of electrical equipment; when the magnitude of voltage falls, BPS will detect the magnitude of negtive voltage two cycles ago to make a decision, that can avoid the process of connecting to permanent fault and tripping again for the ring main unit. EMTP simulation results show the effectiveness of the scheme.
Keywords :
power distribution faults; power distribution protection; EMTP simulation; distribution line automation system; distribution line noncommunication protection; overheating damage; permanent fault; ring main unit; unsymmetrical fault; Automation; Circuit breakers; Circuit faults; Induction motors; Power supplies; Relays; backup power supply; distribution line automation; distribution line non-communication protection; symmetrical fault;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
Type :
conf
DOI :
10.1109/APAP.2011.6180481
Filename :
6180481
Link To Document :
بازگشت