Title :
Low current and flashing HIF detection method
Author :
Dominik, Bak ; Rebizant, W.
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
High Impedance Faults (HIFs) can differ one from another enormously starting from single flashes through arcing faults to permanent ones. New approach to HIF detection is presented in this paper allowing for identification of two latter ones. The novel protection methodology - 3D power protection scheme (3DPPS) was developed to do the job. The proposed solution is fully adaptive and does not require the knowledge of system parameters. The identification of a fault is based on monitoring voltage or current signals and their three phase symmetry deviations which carry all necessary information on the actual state of the protected system.
Keywords :
arcs (electric); fault diagnosis; power distribution protection; 3D power protection scheme; 3DPPS; arcing faults; current signal monitoring; flashing HIF detection method; high impedance faults; three phase symmetry deviations; voltage signal monitoring; Delay; Fault currents; Harmonic analysis; Switches; Three dimensional displays; Vectors; Voltage measurement; 3D power protection scheme; distribution system; electrical arc; high impedance fault;
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
DOI :
10.1109/APAP.2011.6180494