Abstract :
A novel phase selector is proposed based on the multi-parameter comparison of fault components. Each of three phases is used as the reference phase in turn to calculate the positive sequence component and the sum of the zero and negative sequence components. The phase difference between the positive sequence component and the sum of the zero and negative sequence components is calculated under three different reference phases. Therefore, a multi-parameter criterion is proposed based on the three cosine values to accomplish the phase selection. The proposed method has an obvious boundary for faulty phase discrimination. Furthermore, the proposed method has good performance of sensitivity and reliability, and its effectiveness is verified by the simulations.
Keywords :
power transmission faults; power transmission lines; multiparameter comparison criterion; negative sequence components; phase discrimination; phase selector; reliability; sensitivity; transmission line protective relaying; zero sequence components; Automation; Impedance; Power system protection; Relays; Reliability; Resistance; fault component; multi-parameter comparison; phase selection; power system; transmission line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
Type :
conf
DOI :
10.1109/APAP.2011.6180515
Filename :
6180515
Link To Document :
بازگشت