• DocumentCode
    1697210
  • Title

    Protection algorithm for a wind turbine generator based on positive- and negative-sequence fault components

  • Author

    Zheng, Tai-Ying ; Cha, Seung-Tae ; Crossley, Peter A. ; Kang, Yong-Cheol

  • Author_Institution
    Dept. of Electr. Eng., Chonbuk Nat. Univ., Jeonju, South Korea
  • Volume
    2
  • fYear
    2011
  • Firstpage
    1115
  • Lastpage
    1120
  • Abstract
    A protection relay for a wind turbine generator (WTG) based on positive- and negative-sequence fault components is proposed in the paper. The relay uses the magnitude of the positive-sequence component in the fault current to detect a fault on a parallel WTG, connected to the same power collection feeder, or a fault on an adjacent feeder; but for these faults, the relay remains stable and inoperative. A fault on the power collection feeder or a fault on the collection bus, both of which require an instantaneous tripping response, are distinguished from an inter-tie fault or a grid fault, which require a delayed tripping, using the magnitude of the positive-sequence component in the fault current. The fault type is first evaluated using the relationships between the positive and negative-sequence fault components depending on type of fault. Then the magnitude of the positive-sequence component in the fault current is used to decide on either instantaneous or delayed operation. The operating performance of the relay is then verified using various fault scenarios modelled using EMTP-RV. The scenarios involve changes in the position and type of fault, and the faulted phases. Results confirm that the relay can successfully distinguish between faults that require an instantaneous, delayed or non-operation response.
  • Keywords
    fault currents; fault diagnosis; power generation protection; power grids; relay protection; wind power plants; wind turbines; EMTP-RV; adjacent feeder; delayed tripping; fault component; fault current; fault detection; grid fault; instantaneous tripping response; intertie fault; negative sequence component; nonoperation response; parallel WTG; power collection feeder; relay performance verification; relay protection; wind turbine generator protection; Circuit faults; Current measurement; Fault currents; Generators; Power transformer insulation; Relays; Wind farms; Delayed operation; Instantaneous operation; Non-operation; Outage section minimization; Symmetrical components; Wind turbine generator protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Advanced Power System Automation and Protection (APAP), 2011 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-9622-8
  • Type

    conf

  • DOI
    10.1109/APAP.2011.6180548
  • Filename
    6180548