Protection algorithm for a wind turbine generator based on positive- and negative-sequence fault components
Author
Zheng, Tai-Ying ; Cha, Seung-Tae ; Crossley, Peter A. ; Kang, Yong-Cheol
Author_Institution
Dept. of Electr. Eng., Chonbuk Nat. Univ., Jeonju, South Korea
Volume
2
fYear
2011
Firstpage
1115
Lastpage
1120
Abstract
A protection relay for a wind turbine generator (WTG) based on positive- and negative-sequence fault components is proposed in the paper. The relay uses the magnitude of the positive-sequence component in the fault current to detect a fault on a parallel WTG, connected to the same power collection feeder, or a fault on an adjacent feeder; but for these faults, the relay remains stable and inoperative. A fault on the power collection feeder or a fault on the collection bus, both of which require an instantaneous tripping response, are distinguished from an inter-tie fault or a grid fault, which require a delayed tripping, using the magnitude of the positive-sequence component in the fault current. The fault type is first evaluated using the relationships between the positive and negative-sequence fault components depending on type of fault. Then the magnitude of the positive-sequence component in the fault current is used to decide on either instantaneous or delayed operation. The operating performance of the relay is then verified using various fault scenarios modelled using EMTP-RV. The scenarios involve changes in the position and type of fault, and the faulted phases. Results confirm that the relay can successfully distinguish between faults that require an instantaneous, delayed or non-operation response.
Keywords
fault currents; fault diagnosis; power generation protection; power grids; relay protection; wind power plants; wind turbines; EMTP-RV; adjacent feeder; delayed tripping; fault component; fault current; fault detection; grid fault; instantaneous tripping response; intertie fault; negative sequence component; nonoperation response; parallel WTG; power collection feeder; relay performance verification; relay protection; wind turbine generator protection; Circuit faults; Current measurement; Fault currents; Generators; Power transformer insulation; Relays; Wind farms; Delayed operation; Instantaneous operation; Non-operation; Outage section minimization; Symmetrical components; Wind turbine generator protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-9622-8
Type
conf
DOI
10.1109/APAP.2011.6180548
Filename
6180548
Link To Document