DocumentCode :
1699678
Title :
Failure mode for AC drives on high resistance grounded systems
Author :
Tallam, Rangarajan M. ; Schlegel, David W. ; Hoadley, Frederick L.
Author_Institution :
Rockwell Autom., Mequon, WI
fYear :
2006
Abstract :
High resistance grounding (HRG) is the preferred method of grounding in several industrial power distribution systems because of safety and reliability concerns. In this paper, a failure mode for AC drives on HRG systems is investigated. The cause of the failure is identified to be due to the interaction between the EMC circuitry of the drives. Simulation and experimental results are provided to demonstrate the failure mode. User manuals of several drive manufacturers are reviewed and recommendations for operating drives on HRG systems are provided
Keywords :
earthing; electric drives; electromagnetic compatibility; failure analysis; power system reliability; AC drives; EMC circuitry; HRG systems; failure mode; high resistance grounding systems; Circuit faults; Electromagnetic compatibility; Grounding; Manufacturing; Personnel; Power distribution; Power system reliability; Power system simulation; Safety; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied Power Electronics Conference and Exposition, 2006. APEC '06. Twenty-First Annual IEEE
Conference_Location :
Dallas, TX
Print_ISBN :
0-7803-9547-6
Type :
conf
DOI :
10.1109/APEC.2006.1620752
Filename :
1620752
Link To Document :
بازگشت