A novel fault locator for power distribution system with neutral non-effectively grounded
Author :
Shi Shenxing ; Dong Xinzhou
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
Fault locator for power distribution system with neutral non-effectively grounded should locate phase-to-phase fault and single-phase-to-ground fault respectively. For phase-to-phase fault, the point can be located by power-frequency impedance. However, for single-phase-to-ground fault with limited power-frequency current not more than load current, a novel fault location technology should be developed. The paper will present a practical single-phase-to-ground fault location based on fault generated traveling waves acquired from one phase current transducer and zero sequence current transducer at first. Then implementation of the novel fault locator is proposed including hardware design and software flowchart. At last field tests will be made to verify the feasibility of the fault locator.
Keywords :
fault location; power distribution faults; fault locator; load current; neutral noneffective grounded; phase-to-phase fault; power distribution system; power-frequency current; power-frequency impedance; single-phase-to-ground fault; Current measurement; Fault location; Impedance; Power distribution; Random access memory; Voltage measurement; fault locator; power distribution system; single-phase-to-ground fault; traveling waves;